Screen Shots
SensAlert Plus was developed with the user in mind - adding features that make it the easiest to install, use and maintain. The large, clear LCD screen offers a non-intrusive user interface and intuitive menu structure. On 3-wire models the LCD screen is back-lit making it easy to see regardless of the location where it is installed.
Exploded View of SensAlert Plus
Specifications:
Sensors
Types: Toxic, Oxygen and Combustible
Technology: Infrared, catalytic bead and electrochemical
Test-On-DemandTM Modules: Type C and Type S
Electrical
Voltage/Power:
2-Wire nominal 24 VDC (18-30 VDC): Max current 20 mA
3-Wire nominal 24 VDC (12-30 VDC): Max current 90 mA
With Optional Relay Card and Combustible sensors: Max current 300 mA
Output:
3 wire: 4-20 mA
2-wire: 4-20 mA, loop powered
Relay:
Std with 3-Wire non-IS Only: 1 SPDT Configurable Relay
Optional Card : 3 SPDT Configurable Relays
Contact Ratings: 5 Amp at 115 VAC or 30 VDC Resistive
User Interface
Controls
Magnetic Keypad: OK, << (Go Back), ↑, ↓
Security: Password Protected Configuration Menu
Display
LEDs: Four (4) Red, corresponding to magnetic keypad, and Alarm Relays when so equipped.
Graphic LCD: 128 by 64 pixel screen (backlight on 3-wire)
Screen Displays: Concentration and Measuring Units, Gas Name or Type, Sensor Span, Local Date-Time, Tag Number and System messages or Warnings
Environmental
Temperature (Transmitter): -40°F - 167°F / -40°C - 75°C
Temperature (Sensor): See Sensor Data Sheets
Humidity (Sensor): 15% - 95% RH, non-condensing; 0-99% Infrared, non-condensing; 0-90% Catalytic, non-condensing
Enclosure Options
NEMA 4X (IP 56): Fiberglass; IP66 with use of an optional rainshield.
Dimensions: 7.5" W x 12.6" H x 6.2" D 190 mm W x 320 mm H x 157 mm D
Weight Range: 5.5-6.4 lbs /2.5-2.9 kg
Explosion-proof (IP 56): Copper-free, Cast Aluminum
Dimensions: 5.5" W x 12.3" H x 4.6" [6.4"] D140 mm W x 312 mm H x 117 mm [163 mm] D
Weight Range: 6.1-7.9 lbs / 2.8-3.6 kg
Note: [ ] Brackets indicate large dome depth.
Approval Ratings
Explosion Proof
FM NEC/ CEC: Class I Div 1, Groups A, B, C & D, T4; Class II Div 1, Groups E, F & G; Class III Div 1 & 2
ATEX: Eex d[ia] IIC T4 II 2(1) GD
Non-Incendive
FM NEC/ CEC: Class I Div 2, Groups A, B, C, D Class II Groups E, F & G; Class III Div 1 & 2
ATEX: Eex nC [ia] IIC T4 II 3(1) G
Intrinsically Safe
FM NEC/ CEC: Class I Div 1, Groups A, B, C, D, E; Class II, Groups F & G; Class III
ATEX: Eex d ia IIC T4 II 1 G
Approved to FM, CSA, CENELEC and ATEX Standards
CE Mark: EN55011 & EN61000
INMETRO Certified
Note: Refer to certification documents and datasheets for specific approval and configuration information. Consult factory for additional sensor technologies.